06:41PM | 06/24/03
Member Since: 06/04/03
18 lifetime posts
Bvplumbing
After sufficient water usage the sewage pump in my basement will turn on QUIETLY but NO waste water is being moved. It will run like this for hours maybe even days without moving any water. To solve this I unplug the pump for a few seconds. When I re-plug it in you can hear the water being pupmped out. It will then empty the well in a few seconds. Why is it necessary to unplug and plug the pump to get it to work. It sounds like it is running but you can hear that no water is moving until this is done. Could there be something stuck in the "well" that floats up when I unplug the pump, thereby freeing the impeller to turn????? But if the impeller was jamed wouldn't the motor have burned out by now? It will be difficult to open the cover to look in the well so I am hoping for an easy fix. Thanks in advance for the help.

erik peterson

04:53AM | 06/26/03
Member Since: 06/23/03
224 lifetime posts
I think you are losing the "prime" in the pump each time it kicks off..not a pump-expert but I do know there is a specific way of installing the outlet pipe with a weep-hole near the bottom (drilled by the installer) to prevent this problem. erik

nimguy

02:20PM | 06/26/03
Member Since: 06/04/03
18 lifetime posts
Thanks for the info. Anyone know more about "weep holes" like: Where would I find the one that is apparently plugged in my system?? In the well??? Tnx again

erik peterson

02:56PM | 06/26/03
Member Since: 06/23/03
224 lifetime posts
If you have the manual for the pump it will show how and where the hole should be drilled on the discharge side of the pump.If you dont have the paperwork look for the brand/model and request from the manufacturer via internet. erik

plumber Tom

07:24PM | 06/26/03
Member Since: 05/10/03
801 lifetime posts
You can drill a 1/4" weep hole yourself. Simply drill it on the discharge line like Eric said. The easiest way is to disconnect the check valve, and drill it between the male adapter and the check valve. The reason for the weep hole is to drain out the water that is between the discharge side of the pump and the check valve. Naturally if your check vave is not in the sump, this is not feasable. This should hold the prime on the pump. Also if your pump is for effluent discharge you need to periodically clean out the screen.

nimguy

03:24PM | 06/27/03
Member Since: 06/04/03
18 lifetime posts
Thanks Guys for the assist!! I might be able to work this out now.

joed

03:45PM | 07/02/03
Member Since: 09/17/02
524 lifetime posts
Look for an existing hole that has rusted over or become clogged.

nimguy

07:28PM | 07/02/03
Member Since: 06/04/03
18 lifetime posts
Will do Thanks.

nimguy

11:09AM | 07/04/03
Member Since: 06/04/03
18 lifetime posts
Turns out to have been the one way check valve. The tether for the flap was gone. When the pump kicked in it would push the disc/flap against the top of the valve housing. If it got a good seal it prevented the water from leaving so the pump stayed on. This pressure build up caused the rubber sleeves that connect the one way valve to the pipe to burst (yeech!) So all is good now with a new check valve.. Thanks again to everyone for taking the time to help me here.
Click_to_reply_button Inspiration_banner

INSPIRATION GALLERY



Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply_choose_button

captcha
type the code from the image

Anonymous

Post_new_button or Login_button
Register

Follow_banner_a
Newsletter_icon Google_plus Facebook Twitter Pinterest Youtube Rss_icon
 
webapp2