Can anyone tell me what would be the maximum distance away from the toilet I can put the vent?
I live in massachusetts and the toilet drain is 3" venting into a 2" vent pipe downstream. Looking to see how far away from the toilet I can put the 2" vent.
Thanks
COMMUNITY FORUM
For some reason different states feel their toilet water can travel different distances.
Those adopting the Uniform Plumbing Code think six feet at 1/4" and those adopting the International Plumbing Code think 10 feet at 1/8" per foot of fall.
Massachusetts has it's own plumbing code and I have quit trying to find it. You are wanting trap arm distances and they can be found under Traps or Fixture Vents in a code.
Those adopting the Uniform Plumbing Code think six feet at 1/4" and those adopting the International Plumbing Code think 10 feet at 1/8" per foot of fall.
Massachusetts has it's own plumbing code and I have quit trying to find it. You are wanting trap arm distances and they can be found under Traps or Fixture Vents in a code.