Any help is greatly appreciated.
Thanks,
Phil
Any help is greatly appreciated.
Thanks,
Phil
Two more questions...
Does that mean that the thermostats (in each room) connect to the zone valves (relays)?
Then how does the furnace know which pump to run? I have one pump and one zone valve per zone.
Thanks,
Phil
is my exact design - a multiple series circuit using pumps.
The Honewell relays that I described in my initial post, are installed "in line" (in the pipe), and are essentially automated valves that open or close depending upon the call for heat to that zone. Perhaps I shouldn't have refered to them a "relays".
Phil
I have a multi zone system, with one taco pump per zone. Don't I need a multi zone control panel and acquastat to control each zone? Or can I really simply wire the pumps and thermostats in series to the two sets of leads (respectively) coming out of the furnace?
Thanks,
Phil
Just to verify the wiring, I presume it should go like this.
1) Regular 110V house current to the Weil McLain CGi unit.
2) Regular 110V house current to the Taco circulator relay.
3) Thermostats to the Taco circulator relay.
4) Taco circulator relay to the Taco pumps.
5) Taco circulator relay to the thermostat leads coming from the Weil McLain CGi unit.
And then, cap off the one set of cirulator leads coming from the Weil McLain CGi unit.
Does that appear correct?
Thanks again for all your help,
Phil
P.S. I almost forgot. Step 6) Return the Honeywell Zone Valves!
Just one more question....the relay shows two terminals that are marked "X" and also marked "End Switch". On the instructions, these show as being connected to "TT on Boiler", or "TT on the Acquastat". Do I connect these terminals to the CGi boiler's thermostat connection, or add an Acquastat into the picture (not sure what an Acquastat is anyway)?
Thanks,
Phil
Phil
Phil
After I swapped the zone valves with the flow valves, I realized that I could have probably kept the zone valves there. They are closed when not powered, and if I figured a way to get them 24 volts power (maybe a transformer between them and their circulator pump), then they would only open when their zone is activated. This would essentially provide the same service as the flow check valves - preventing backflow when one zone is on and another if not.
But then, more "stuff" to brake down I suppose.
Thanks again,
Phil