Bvhvac
Installing the Y8610 U 3003 in a Dayton 3E240 unit heaterthermostat.. Heater has 3 (W-R-Bl) wires coming from, I assume the internal fan thermostat. Having trouble figuring out where to put these 3, with the wire coming from the th-w terminal on the module and the 2 thermostat wires from the regular thermostat. I know I need one 24v from the transformer. Do I need a 3rd wire to go to the thermostat? I have the orange wire from the 24v GRD to the ground terminal on the gas valve. Is that OK or should that go to the ignitor or chassis? I need the black wire from the th-w terminal on the module to go where?

I purchased a new Honeywell t-stat today.

Thanks for the help.

jbolive

05:12AM | 12/22/06
Member Since: 09/04/06
6 lifetime posts
Got it working. Had to move the ignitor as it was too close to the frame and was grounding out. Working fine now. Page 14 does not have all the wires I had coming from the heater.

Thanks!