COMMUNITY FORUM

jam7340

06:49AM | 01/05/10
Member Since: 01/04/10
3 lifetime posts
Bvhvac
I've noticed two problems with my heating system, but not sure if they are related. Here's the background - sorry for being so long winded.

Background:

I have a Weil-Mclain Gold CGi Series 2 (which was probably installed in the 2002/2003 time frame). I have four zones:

Zone 1 - main floor

Zone 2 - upstairs (bedrooms)

Zone 3 - indirect water heater

Zone4 - radiant floor in the kitchen

I also use Honeywell programmable thermostats for zones 1 and 2, and a manual thermostat for zone 4.

At night, the temperature for zone 1 (downstairs) is programmed to drop from 66 to 62 and zone 2 is set for 66.

Problem 1:

On at least 3 or 4 occasions now in the last month, right before bed, I do a final check and have noticed zone 2 (upstairs) drop to as low as 63 (about 1 degree higher than downstairs), even though it is set for 66. My guess is that it is no longer switching on, but the downstairs heat is rising and keeping it at 63. Switching the thermostat from heat to off and then back to heat again seems to reset it and all seems to work fine for the rest of the night - with one exception...

Problem 2:

Again, not sure if this is related or not, but since my bedroom is above the furnace room, I can hear the furnace blower when it turns on, and several times now, I've heard it cycle on for about 10 or 15 seconds, then off, then on. It does this 3 or 4 times before finally cycling on and staying on for several minutes. The following morning, when zone 1 starts requesting heat, I don't notice this cycling problem anymore.

Any thoughts?

jam7340

08:41AM | 01/05/10
Member Since: 01/04/10
3 lifetime posts
I'm not sure I understand your reply.

Just to add a little more detail to my setup, I have two air handlers located in the attic (for zones 1 and 2). It's a hydro-air system, and each one works independently.

Can you reword you response and help me understand what is causing zone 2 (upstairs) to shut down intermittently until i reset the thermo by turning it off and on?

Also, and possibly unrelated, why is it that I'm not noticing the short cycling happening in the morning (or the rest of the day for that matter)?

jam7340

08:40AM | 01/06/10
Member Since: 01/04/10
3 lifetime posts
HVAC guy came out today. Felt it was a sticky relay in the air handler and replaced it. Items leading to this decision were:

1. Boiler appeared to be working since other zones were not having any problems (though the occasional cycling of the boiler is still a mystery)

2. Hot water was getting to the air handler - so the pumps were working as well.

3. Air was not blowing from the handler when it should have been. Turning the stat to manual fan would begin blowing hot air, but when set to auto - sometimes would work, sometimes wouldn't

4. Turning stat off and back on would sometimes fix the problem - probably because it would reset the relay.

Regarding the boiler cycling issue - recommended a boiler cleaning and keeping an eye on it to see if the flame sensor is going bad.

My heating system is hydro-air and zones 1 and 2 are each managed by a separate air handler.
Click_to_reply_button
Inspiration_banner

INSPIRATION GALLERY



Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply_choose_button

captcha
type the code from the image

Anonymous

Post_new_button or Login_button
Register

The Infinite Artisan Fire Bowl from Eldorado Outdoor is made from glass-fiber reinforced concrete, and offered in Oak Barr... Built on a rocky island in the Drina River, near the town of Bajina Basta, Serbia, this wooden house was cobbled together ... Large steel-framed windows flood the interior of this remodeled Michigan barn with daylight. The owners hired Northworks A... Edging formed with upside-down wine bottles is a refreshing change. Cleverly and artistically involving recycled materials... A Washington State couple called on BC&J Architects to transform their 400-square-foot boathouse into a hub for family bea... Similar to the elevated utensil concept, hanging your pots and pans from a ceiling-mounted rack keeps them nearby and easy... Few projects are more fun than upcycling a vintage piece in a surprising way. Outfitted with a sink and a delicately tiled... The thyme growing between these stepping stones adds a heady fragrance to strolls along this lush, low-maintenance garden ... Decoupage is an easy way to add any paper design to your switch plate, whether it is wallpaper, scrapbook paper, book page... Twine lanterns add pops of crafty—but sophisticated—flair to any outdoor setting. Wrap glue-soaked twine around a balloon ... When securely fastened to a tree or the ceiling of a porch, a pallet and some cushioning make the ideal place to lounge. V... Reluctant to throw away any of those unidentified keys in your junk drawer? Hang them from a few chains attached to a simp... A stripped-down model, sans screened porch, starts out at $79,000. Add the porch, a heated floor for the bath, and all the... Salvaged boards in varying widths and colors make up the dramatic accent wall in this attic space. The high-gloss white of... This garden shed has been decked out to the nines. Designer Orla Kiely created the intimate home for a flower trade show, ...
Follow_banner_a
Newsletter_icon Google_plus Facebook Twitter Pinterest Youtube Rss_icon
 
webapp1