How can I tell the difference between 60 degree wiring and 90 degree wiring?

CHOLE4ELECTRIC

12:50PM | 02/05/00
Member Since: 10/24/99
31 lifetime posts
Dear Shuanm:
Here is the article in the 1999 National Electrical Code Book (the latest edition)
(personal observation: the indivual contuctor of 90º wire is very shinny)
310-11. Marking
(a):
Required Information. All conductors and cables shall be marked to indicate the following information, using the applicable method described in
(b):
1. The maximum rated voltage for which the conductor was listed
2. The proper type letter or letters for the type of wire or cable as specified elsewhere in this Code
3. The manufacturer’s name, trademark, or other distinctive marking by which the organization responsible for the product can be readily identified
4. The AWG size or circular mil area
5. Cable assemblies where the neutral conductor is smaller than the ungrounded conductors shall be so marked
(b) Method of Marking.
(1) Surface Marking. The following conductors and cables shall be durably marked on the surface. The AWG size or circular mil area shall be repeated at intervals not exceeding 24 in. (610 mm). All other markings shall be repeated at intervals not exceeding 40 in. (1.02 m).
a. Single- and multiconductor rubber- and thermoplastic-insulated wire and cable
b. Nonmetallic-sheathed cable
c. Service-entrance cable
d. Underground feeder and branch-circuit cable
e. Tray cable
f. Irrigation cable
g. Power-limited tray cable
h. Instrumentation tray cable
(2) Marker Tape. Metal-covered multiconductor cables shall employ a marker tape located within the cable and running for its complete length.
Exception No. 1: Mineral-insulated, metal-sheathed cable.
Exception No. 2: Type AC cable.
Exception No. 3: The information required in Section 310-11(a) shall be permitted to be durably marked on the outer nonmetallic covering of Type MC, Type ITC, or Type PLTC cables at intervals not exceeding 40 in. (1.02 m).
Exception No. 4: The information required in Section 310-11(a) shall be permitted to be durably marked on a nonmetallic covering under the metallic sheath of Type ITC or Type PLTC cable at intervals not exceeding 40 in. (1.02 m).
FPN: Included in the group of metal-covered cables are Type AC cable (Article 333), Type MC cable (Article 334), and lead-sheathed cable.
(3) Tag Marking. The following conductors and cables shall be marked by means of a printed tag attached to the coil, reel, or carton:
a. Mineral-insulated, metal-sheathed cable
b. Switchboard wires
c. Metal-covered, single-conductor cables
d. Conductors that have an outer surface of asbestos
e. Type AC cable
(4) Optional Marking of Wire Size. The information required in (a)(4) shall be permitted to be marked on the surface of the individual insulated conductors for the following multiconductor cables:
a. Type MC cable
b. Tray cable
c. Irrigation cable
d. Power-limited tray cable
e. Power-limited fire alarm cable
f. Instrumentation tray cable
(c) Suffixes to Designate Number of Conductors. A type letter or letters used alone shall indicate a single insulated conductor. The letter suffixes shall be indicated as follows:
D — For two insulated conductors laid parallel within an outer nonmetallic covering
M — For an assembly of two or more insulated conductors twisted spirally within an outer nonmetallic covering
(d) Optional Markings. All conductors and cables contained in Chapter 3 shall be permitted to be surface marked to indicate special characteristics of the cable materials.
FPN: Examples of these markings include but are not limited to “LS” for limited smoke and markings such as “sunlight resistant.”

I know there's a lot there to absorb, if you have any trouble with any of that just pick out the part you don't understand I will try to make it clearer.

shaunm

04:15PM | 02/05/00
Member Since: 02/04/00
2 lifetime posts
I'm wanting to replace some old light fixtures with newer ones. The new fixtures warn "houses built before 1985 have 60 degree wire" and the fixture requires 90 degree wire. Short of calling an electrician, is there some way I can tell which wire I have? Thanks.

CHOLE4ELECTRIC

05:29PM | 02/05/00
Member Since: 10/24/99
31 lifetime posts
if your house wasn't built after 1985 it's a good bet that you don't have wire rated for 90º .....
Click_to_reply_button
Inspiration_banner

INSPIRATION GALLERY



Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply_choose_button

Anonymous

Post_new_button or Login_button
Register

Even the simplest holiday decorations can achieve a high visual impact. Here, an unadorned garland held in place with whit... Filling an underutilized area beneath the stairs is a smart way to save space. Doing so with a stash of wood, however, is ... The Audubon Society inspired wallpaper in this Adirondack-styled entryway will get you in the outdoor mood. Grab your coat... Chalkboard paint opens up endless possibilities for customizing your dresser time and time again. Use chalk to label the c... A fireplace in the bathroom creates the ultimate setting for relaxation. Homeowners often choose electric or gas over wood... This roomy boot tray made from punched metal stands up to all the elements. Station it in your mudroom or at your back doo... There’s nothing like a new set of cabinet hardware to refresh a room. The possibilities are endless: Go modern, rustic, or... FLOR carpet tiles are a simple and affordable way to customize a floor covering for any space. You can make anything from ... Chalkboard paint features prominently in this elegant yet unpretentious headboard design. Add a new message daily to reflec... Salvaged boards in varying widths and colors make up the dramatic accent wall in this attic space. The high-gloss white of... The indecisive homeowner need not fret over choosing one (or even two) cabinet colors. The kitchen cabinets in this artist... Incorporate nature into your lighting scheme by securing a dead tree in a concrete mold and draping your pendant lamp from... Simple and striking, a couple of pieces of "lovingly used" furniture creates a special kind of charm. A weathered chair fo... First dress up your metal shelves with a coat of paint in an accent color that complements your kitchen decor. Then arrang... The vibrant green of Granny Smith apples make a beautifully natural alternative to the traditional evergreen wreath. Brigh...
Follow_banner_a
Newsletter_icon Google_plus Facebook Twitter Pinterest Youtube Rss_icon