Bvelectrical
HELP! I am finishing my basement and am putting in baseboard heat. I am buying (3) 6 foot Cadet heaters with a thermostat. I am assuming I need to run 12/3 wire to the box. (Or is it 12/2?) But what I am wondering is how many circuits do I need to run for these? Do I need to run a circuit for each? Or can I get away with running one circuit for all three? I am sure there is a calculation for this but I need some solid advice. Thanks!!!!

joed

03:35AM | 12/30/02
Member Since: 09/17/02
527 lifetime posts
How many watts are these heaters. That will determin the number of circuits and the size of the wire and breakers.

jteter

05:27AM | 12/30/02
Member Since: 12/26/02
6 lifetime posts
The heaters are 240V, 1500 Watts, 6.25 AMPs, 5118 BTUs each.

Mycroft

12:48PM | 12/30/02
Member Since: 12/28/02
2 lifetime posts
2-20 amp circuit using 12/2w.g. with two thermostats or you could run 1-30 amp 10/2w.g. circuit if the thermostat is rated for 30 amps.
The formula for electric space heating is total ampacity X 125%
6.25 amps * 1 = 6.25 *125% = 8.72 A
6.25 amps * 2 = 12.50 * 125% = 15.63 A
6.25 amps * 3 = 18.75 amps * 125% = 23.437 A
12/2 can handle a 16 amp continuous load
10/2 can handle 24 amps
Hope this helps

jteter

02:16AM | 12/31/02
Member Since: 12/26/02
6 lifetime posts
Thank you so much for your help!!!! I was planning on the 30 amp route, but I can't seem to find a T-stat that is rated for 30. So I am going to go the (2) 20s route. Thanks again!

tdhorne

06:13AM | 01/01/03
Member Since: 09/01/02
31 lifetime posts
Please check the label on the heater! If the label on the heater specifies a circuit size and/or Over Current Protective Device (OCPD) and that label also bares the testing agency listing mark you must use that size of circuit and/or OCPD.
--
Tom

harold endean

08:23AM | 01/01/03
Member Since: 08/30/02
23 lifetime posts
By the way, a 12-2 Non metallic sheathed cable also called sheathed electrical cable or,RX wire means that there is inside the cable a black wire, a white wire and a ground (bare) wire in the cable. A 12-3 wire means that there is an extra red wire inside the cable.

winkleal

03:01PM | 01/11/03
Member Since: 11/10/02
6 lifetime posts
Mycroft

How did you come up with 12/2 only able to handle 16A continuous load? In Annex B of 2002 Code, Table B.310.1, the lowest ampacity listed for copper wire is 20A. I think you are derating twice. Once for the load when you use the demand current and multiply by 125%, and again when you state that 12/2 is only good for 16A

Tony

[This message has been edited by winkleal (edited January 11, 2003).]

Click_to_reply_button Inspiration_banner

INSPIRATION GALLERY



Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply_choose_button

captcha
type the code from the image

Anonymous

Post_new_button or Login_button
Register

Follow_banner_a
Newsletter_icon Google_plus Facebook Twitter Pinterest Youtube Rss_icon
 
webapp1