Can a bathroom GFCI outlet be on the same circuit as "regular" outlets? Or does it need to be on a circuit that only carries load to GFCI outlets?
COMMUNITY FORUM
- Forum >
- Electrical & Lighting >
- Bathroom GFCI on own circuit
210.11(C)(3) Generally, the 20 amp GFCI bathroom circuit may supply only the bathroom receptacle outlets. An exception is made where the bathroom circuit serves only a single bathroom; you can use the circuit for other equipment in the same bathroom as long as you do not exceed 210.23(A).