I have two 8.4 Amp, 110V air conditioners to install at home on the same end of the loft. In the ceiling there is a 30A circuit feeding five 100w light bulbs in ceiling fixtures, and that's everything on the circuit right now. (There are no outlets on the circuits, just the five fixtures for the five bulbs.)

Can someone tell me if it is safe and legal for me to extend this line to provide outlets for the air conditioners?

Thanks!

dana1028

10:59AM | 07/10/03
Member Since: 08/30/02
32 lifetime posts
I imagine your window AC's are 'cord connected' and use a standard 15A rated plug connector.
At issue here is the 30A circuit - all the wiring, receptacles, cord connections would be required to be rated 30A....Not Likely given your ACs probably have 15A rated plug connection. The mfr. label on the ACs should indicate the maximum circuit rating (prob. not over 20A).

Am kind of curious though - what are you doing with a 30A rated circuit for a few light fixtures?...I'm wondering if that circuit was ever sized properly (i.e. what size is the wiring on that circuit? ...since this is a lighting circuit it just may have been wired with #14 [thus a 15A max rated circuit]and someone put the wrong breaker in....something to check).

[This message has been edited by dana1028 (edited July 10, 2003).]

Opie

03:15PM | 07/10/03
Member Since: 07/09/03
2 lifetime posts
After I posted the question I began to wonder about the rating of the wiring too.

No, it isn't sized properly, it's 12 gauge.
This is a loft where the landlord started a haphazard conversion 25 years ago and still hasn't finished. I'm sure the breaker was an error.

My new plan was to re-route the lights to a 20A circuit that usually carries about 10A, and then run new conduit also with 12 gauge wire and dedicate it to the air conditioners.

BUT, from what you are saying running them on the 30A breaker is most likely problematic even if I'm staying within 20 amps for the wiring. (The ac's arrive tomorrow so that's when I'll know the max. circuit size.)

I am currently in court with the landlord on other matters and I doubt I'll get quick action from him to swap the 30 for a 20. As a stop gap measure would it risk life and/or air conditioner to proceed as planned but put a 15 amp power strip between each unit and it's receptacle, (and seal up the other outlets in each strip). I say 15 instead of 10 because I've never seen a 10 amp power strip. It would be temporary as the landlord is required to upgrade the power to our unit anyway and the breaker would be swapped out then.

[This message has been edited by Opie (edited July 10, 2003).]

Click_to_reply_button
Inspiration_banner

INSPIRATION GALLERY



Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply_choose_button

Anonymous

Post_new_button or Login_button
Register

As pretty as it is simple to arrange, this window decoration features miniature wreaths hung from red ribbon of varying le... Filling an underutilized area beneath the stairs is a smart way to save space. Doing so with a stash of wood, however, is ... The Audubon Society inspired wallpaper in this Adirondack-styled entryway will get you in the outdoor mood. Grab your coat... Chalkboard paint opens up endless possibilities for customizing your dresser time and time again. Use chalk to label the c... A fireplace in the bathroom creates the ultimate setting for relaxation. Homeowners often choose electric or gas over wood... This roomy boot tray made from punched metal stands up to all the elements. Station it in your mudroom or at your back doo... There’s nothing like a new set of cabinet hardware to refresh a room. The possibilities are endless: Go modern, rustic, or... FLOR carpet tiles are a simple and affordable way to customize a floor covering for any space. You can make anything from ... Chalkboard paint features prominently in this elegant yet unpretentious headboard design. Add a new message daily to reflec... Salvaged boards in varying widths and colors make up the dramatic accent wall in this attic space. The high-gloss white of... The indecisive homeowner need not fret over choosing one (or even two) cabinet colors. The kitchen cabinets in this artist... Incorporate nature into your lighting scheme by securing a dead tree in a concrete mold and draping your pendant lamp from... Simple and striking, a couple of pieces of "lovingly used" furniture creates a special kind of charm. A weathered chair fo... First dress up your metal shelves with a coat of paint in an accent color that complements your kitchen decor. Then arrang... The vibrant green of Granny Smith apples make a beautifully natural alternative to the traditional evergreen wreath. Brigh...
Follow_banner_a
Newsletter_icon Google_plus Facebook Twitter Pinterest Youtube Rss_icon