The top of the panel has no more entrance holes and each of the existing holes has two or three wires in them. Can I use the holes that are on the side?

I see that the electricians that wired the house twisted two ground wires and put them in the ground bar, is this acceptable for neutral wires as well?

Any help would be appreciated!

Thanks,

PJI

tperez

05:48PM | 11/05/04
Member Since: 09/24/04
128 lifetime posts
You can use the side K.O.'s but make sure that they are protected especially if the panel is surface mounted. You wouldn't want to bang them up by accident.

Each wire should be in it's own termination lug. Double lugging is not acceptable and can be a dangerous practice.

Do you have any room left in this panel? This panel sounds pretty full to me.

U.S.M.C. Semper Fi !!!

piaccarino

06:21PM | 11/05/04
Member Since: 07/01/04
4 lifetime posts
When I started there were 7 positions open in the 200amp panel. Even before I started adding circuits there were hardly any openings on the neutral bars. Does double lugging apply to neutral and ground wire?

Tom O

01:58AM | 11/06/04
Member Since: 09/17/02
487 lifetime posts
Take a look at the labels inside your breaker box. It will usually tell you the acceptable range of wires. Most bus bars holes are acceptable for two equipment grounds of the same size, but you don't know for sure unless you read the label. Two neutrals in one hole or a neutral and ground in one hole is not acceptable in the NEC, so if your panel is old enough to show two neutrals in one hole, ignore that info.

Tom

piaccarino

04:01AM | 11/08/04
Member Since: 07/01/04
4 lifetime posts
The panel is new as the house was built in April, so I did a little research on the Square D QO panel and found that I can add ground bus bars which will solve my problem of having too few locations for ground/neutral wires. Since it didn't mention it in the bus bar installation instructions, I am assuming that the entire box is ground because it doesn't ask for a wire to run between the existing bars and the ones I purchased to mount to the back wall of the box. Is that correct or do I need to ground these new bars?

Thanks again guys!

PJI

tperez

06:14AM | 11/08/04
Member Since: 09/24/04
128 lifetime posts
That is correct. The panel itself is part of the grounding path. The panel back and/or side should have prefab holes for grounding bars. Use these holes and screws that came with the grounding bar. Self tapping screws are not listed for this purpose and will not provide a good bond.

U.S.M.C. Semper Fi !!!
Click_to_reply_button
Inspiration_banner

INSPIRATION GALLERY



Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply_choose_button

captcha
type the code from the image

Anonymous

Post_new_button or Login_button
Register

Few projects are more fun than upcycling a vintage piece in a surprising way. Outfitted with a sink and a delicately tiled... Built on a rocky island in the Drina River, near the town of Bajina Basta, Serbia, this wooden house was cobbled together ... Large steel-framed windows flood the interior of this remodeled Michigan barn with daylight. The owners hired Northworks A... Edging formed with upside-down wine bottles is a refreshing change. Cleverly and artistically involving recycled materials... A Washington State couple called on BC&J Architects to transform their 400-square-foot boathouse into a hub for family bea... Similar to the elevated utensil concept, hanging your pots and pans from a ceiling-mounted rack keeps them nearby and easy... For windows, doors, and mirrors that could use a little definition, the Naples Etched Glass Border adds a decorative flora... The thyme growing between these stepping stones adds a heady fragrance to strolls along this lush, low-maintenance garden ... Decoupage is an easy way to add any paper design to your switch plate, whether it is wallpaper, scrapbook paper, book page... Twine lanterns add pops of crafty—but sophisticated—flair to any outdoor setting. Wrap glue-soaked twine around a balloon ... When securely fastened to a tree or the ceiling of a porch, a pallet and some cushioning make the ideal place to lounge. V... Reluctant to throw away any of those unidentified keys in your junk drawer? Hang them from a few chains attached to a simp... A stripped-down model, sans screened porch, starts out at $79,000. Add the porch, a heated floor for the bath, and all the... Salvaged boards in varying widths and colors make up the dramatic accent wall in this attic space. The high-gloss white of... This garden shed has been decked out to the nines. Designer Orla Kiely created the intimate home for a flower trade show, ...
Follow_banner_a
Newsletter_icon Google_plus Facebook Twitter Pinterest Youtube Rss_icon
 
webapp1