Bvelectrical
The top of the panel has no more entrance holes and each of the existing holes has two or three wires in them. Can I use the holes that are on the side?

I see that the electricians that wired the house twisted two ground wires and put them in the ground bar, is this acceptable for neutral wires as well?

Any help would be appreciated!

Thanks,

PJI

tperez

05:48PM | 11/05/04
Member Since: 09/24/04
128 lifetime posts
You can use the side K.O.'s but make sure that they are protected especially if the panel is surface mounted. You wouldn't want to bang them up by accident.

Each wire should be in it's own termination lug. Double lugging is not acceptable and can be a dangerous practice.

Do you have any room left in this panel? This panel sounds pretty full to me.

U.S.M.C. Semper Fi !!!

piaccarino

06:21PM | 11/05/04
Member Since: 07/01/04
4 lifetime posts
When I started there were 7 positions open in the 200amp panel. Even before I started adding circuits there were hardly any openings on the neutral bars. Does double lugging apply to neutral and ground wire?

Tom O

01:58AM | 11/06/04
Member Since: 09/17/02
477 lifetime posts
Take a look at the labels inside your breaker box. It will usually tell you the acceptable range of wires. Most bus bars holes are acceptable for two equipment grounds of the same size, but you don't know for sure unless you read the label. Two neutrals in one hole or a neutral and ground in one hole is not acceptable in the NEC, so if your panel is old enough to show two neutrals in one hole, ignore that info.

Tom

piaccarino

04:01AM | 11/08/04
Member Since: 07/01/04
4 lifetime posts
The panel is new as the house was built in April, so I did a little research on the Square D QO panel and found that I can add ground bus bars which will solve my problem of having too few locations for ground/neutral wires. Since it didn't mention it in the bus bar installation instructions, I am assuming that the entire box is ground because it doesn't ask for a wire to run between the existing bars and the ones I purchased to mount to the back wall of the box. Is that correct or do I need to ground these new bars?

Thanks again guys!

PJI

tperez

06:14AM | 11/08/04
Member Since: 09/24/04
128 lifetime posts
That is correct. The panel itself is part of the grounding path. The panel back and/or side should have prefab holes for grounding bars. Use these holes and screws that came with the grounding bar. Self tapping screws are not listed for this purpose and will not provide a good bond.

U.S.M.C. Semper Fi !!!
Click_to_reply_button
Inspiration_banner

INSPIRATION GALLERY



Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply_choose_button

Anonymous

Post_new_button or Login_button
Register

With nothing more than a saw and some plywood, you can create your own Christmas tree cutout forest. Give the "tree" a coa... Filling an underutilized area beneath the stairs is a smart way to save space. Doing so with a stash of wood, however, is ... The Audubon Society inspired wallpaper in this Adirondack-styled entryway will get you in the outdoor mood. Grab your coat... Chalkboard paint opens up endless possibilities for customizing your dresser time and time again. Use chalk to label the c... A fireplace in the bathroom creates the ultimate setting for relaxation. Homeowners often choose electric or gas over wood... This roomy boot tray made from punched metal stands up to all the elements. Station it in your mudroom or at your back doo... There’s nothing like a new set of cabinet hardware to refresh a room. The possibilities are endless: Go modern, rustic, or... FLOR carpet tiles are a simple and affordable way to customize a floor covering for any space. You can make anything from ... Chalkboard paint features prominently in this elegant yet unpretentious headboard design. Add a new message daily to reflec... Salvaged boards in varying widths and colors make up the dramatic accent wall in this attic space. The high-gloss white of... The indecisive homeowner need not fret over choosing one (or even two) cabinet colors. The kitchen cabinets in this artist... Incorporate nature into your lighting scheme by securing a dead tree in a concrete mold and draping your pendant lamp from... Simple and striking, a couple of pieces of "lovingly used" furniture creates a special kind of charm. A weathered chair fo... First dress up your metal shelves with a coat of paint in an accent color that complements your kitchen decor. Then arrang... The vibrant green of Granny Smith apples make a beautifully natural alternative to the traditional evergreen wreath. Brigh...
Follow_banner_a
Newsletter_icon Google_plus Facebook Twitter Pinterest Youtube Rss_icon