The top of the panel has no more entrance holes and each of the existing holes has two or three wires in them. Can I use the holes that are on the side?

I see that the electricians that wired the house twisted two ground wires and put them in the ground bar, is this acceptable for neutral wires as well?

Any help would be appreciated!

Thanks,

PJI

tperez

05:48PM | 11/05/04
Member Since: 09/24/04
128 lifetime posts
You can use the side K.O.'s but make sure that they are protected especially if the panel is surface mounted. You wouldn't want to bang them up by accident.

Each wire should be in it's own termination lug. Double lugging is not acceptable and can be a dangerous practice.

Do you have any room left in this panel? This panel sounds pretty full to me.

U.S.M.C. Semper Fi !!!

piaccarino

06:21PM | 11/05/04
Member Since: 07/01/04
4 lifetime posts
When I started there were 7 positions open in the 200amp panel. Even before I started adding circuits there were hardly any openings on the neutral bars. Does double lugging apply to neutral and ground wire?

Tom O

01:58AM | 11/06/04
Member Since: 09/17/02
477 lifetime posts
Take a look at the labels inside your breaker box. It will usually tell you the acceptable range of wires. Most bus bars holes are acceptable for two equipment grounds of the same size, but you don't know for sure unless you read the label. Two neutrals in one hole or a neutral and ground in one hole is not acceptable in the NEC, so if your panel is old enough to show two neutrals in one hole, ignore that info.

Tom

piaccarino

04:01AM | 11/08/04
Member Since: 07/01/04
4 lifetime posts
The panel is new as the house was built in April, so I did a little research on the Square D QO panel and found that I can add ground bus bars which will solve my problem of having too few locations for ground/neutral wires. Since it didn't mention it in the bus bar installation instructions, I am assuming that the entire box is ground because it doesn't ask for a wire to run between the existing bars and the ones I purchased to mount to the back wall of the box. Is that correct or do I need to ground these new bars?

Thanks again guys!

PJI

tperez

06:14AM | 11/08/04
Member Since: 09/24/04
128 lifetime posts
That is correct. The panel itself is part of the grounding path. The panel back and/or side should have prefab holes for grounding bars. Use these holes and screws that came with the grounding bar. Self tapping screws are not listed for this purpose and will not provide a good bond.

U.S.M.C. Semper Fi !!!
Click_to_reply_button
Inspiration_banner

INSPIRATION GALLERY



Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply_choose_button

captcha
type the code from the image

Anonymous

Post_new_button or Login_button
Register

Colorful, useful, and fun, these tire planters form the foundation for a delightful container garden. Just spray-paint old... Reused steel windows create an eye-catching splashguard in this walk-in shower. The vintage factory windows bring an inter... A galvanized steel tub is a surprising but charming fixture in this bright and breezy screened patio. It's perfect for was... If you're not crazy about the idea of commingling plants and pool, this modern variation may be more to your liking. The s... Yes, a freestanding garage can become its own tiny house. Artist Michelle de la Vega has all the comforts of a modern resi... If you lack plumbing skills but have a good sturdy tree, here's the easiest outdoor shower solution of all: Simply attach... Pursue what's known as the stack effect. To achieve it, open the windows on both the upper and lower floors, and as warm a... How do you like this smart use for an old bottle? Clamp an empty wine bottle to a fence or wall near your outdoor deck or ... Simple and striking, a couple of pieces of "lovingly used" furniture creates a special kind of charm. A weathered chair fo... Twine lanterns add pops of crafty—but sophisticated—flair to any outdoor setting. Wrap glue-soaked twine around a balloon ... When securely fastened to a tree or the ceiling of a porch, a pallet and some cushioning make the ideal place to lounge. V... Incorporate nature into your lighting scheme by securing a dead tree in a concrete mold and draping your pendant lamp from... For the cost of a can of exterior paint , you can totally transform your porch. Paint the floor a hue that complements yo... In this urban apartment, a standard-issue patio became a serene and green perch by replacing the typical concrete with gro... This garden shed has been decked out to the nines. Designer Orla Kiely created the intimate home for a flower trade show, ...
Follow_banner_a
Newsletter_icon Google_plus Facebook Twitter Pinterest Youtube Rss_icon
 
webapp2