I'm adding a 100 amp subpanel to my 200 amp service. I plan on running #2 copper to the subpanel, but am unsure as how to protect it. Is flexible conduit Ok? If so what size?

Also, do I need a breaker in the main panel or can I just use a 100 amp breaker in the sub panel?

Thanks,

Zack

househelper

10:00AM | 02/17/06
Member Since: 03/31/05
265 lifetime posts
You don't have to use #2 Cu, #4 Cu would be fine. Run four wires (3 #4THHN Cu and 1 #8THHN Cu) in a 1.25 schedule 80 PVC conduit. The wires should originate from a breaker in the main panel, you do not have to have a breaker in the subpanel unless it is in a separate building or local codes require it.

How far away will the sub be?

zackivan

07:58AM | 02/21/06
Member Since: 10/02/05
26 lifetime posts
Thanks for your reply. The panels will only be a few feet apart.