COMMUNITY FORUM

fmarti4922

07:27AM | 11/22/09
Member Since: 11/21/09
1 lifetime posts
Bvelectrical
My house had a subpanel in the bedroom closet that was being fed from a main panel outside the house. I am in the process of upgrading to a single 200Amp main panel and replacing the subpanel with a 10in x 10in x 4in junction box in the attic fed by seperate circuits from the main. At this time there are 6 15 amp circtuis feed in this manner. Can anyone tell me whether the code allows a single ground wire from the main connected to a ground bar inside the junction box or whether seperate ground lines for each circuit bonded to the junction box are required?

Tom O

10:15AM | 11/25/09
Member Since: 09/17/02
487 lifetime posts
If your circuits are going to run in a raceway, then one equipment ground will be all you need. If the circuits will be run as individual cables,such as non-metallic sheathed cable, each cable would need its own equipment ground