Retrofit?
If this is on an existing flat wall, use the Arlington 8161 siding block. http://www.aifittings.com/k_6.htm
If this is on an existing flat wall, use the Arlington 8161 siding block. http://www.aifittings.com/k_6.htm
1
answers160
ViewsCheck for power at the box, double check the wiring, make sure any switches are on, check the DIP switches on the remote and receiver to make sure ...
1
answers698
ViewsHow are the red and black wires connected at the breakers? They need to be on breakers that are mounted one above the other so that each is on a di...
13
answers528
ViewsIf you are looking at using an electric on demand, make sure you have sufficient capacity to support it. The electric units require a 70-80 amp sup...
1
answers691
ViewsYou can still find the plastic GE load centers, but you are looking at only 4-6 circuits. Check your local hardware store.
2
answers756
ViewsThe oil will retain heat longer due to its higher viscosity, but as Bill points out, it will cost the same to heat either.
4
answers598
ViewsAt the first GFCI receptacle you will have 12/3 in, 12/2 out to the next GFCI (other circuit) and 12/2 out to the first protected receptacle on cir...
3
answers908
ViewsDo the instructions say it requires a 30A circuit or that it draws 30A? Big difference. If a 30A circuit is required, then 10/3 with ground and a 3...
5
answers35
ViewsThe NEC does not require you to secure NM wiring when fishing inside finished walls.
4
answers797
Views"the voltage on one leg can exceed 250 volts while the other leg can fall to almost zero." For a loose neutral connection, that is not true. The...
7
answers217
Viewsand because it is a trailer, you will need 4 wires (H, H, N, G). There are direct burial quadriplex cables available for use as a mobile home feede...
3
answers514
ViewsCorrectly called an open neutral. Biggest offenders are squirrels. They like to chew on the uninsulated aluminum. Many jurisdictions are going to c...
7
answers90
ViewsAt the ceiling fan you should connect the white to white, black to black, and blue to red. At the switch, for the cable from the ceiling, connec...
2
answers893
ViewsSince this is in a basement, you may have a GFCI receptacle (rectangular receptacle with "test" and "reset" buttons) protecting a portion of that c...
4
answers179
ViewsSince you are routing the feeder through the attic, you will need to use #2 Cu or 1/0 Al according to Table 310-15 (b)(6).
3
answers705
ViewsDoes your panel have a main breaker that can be shutoff? If so, does the fan/light go off then? If not, try turning all the breakers off at the sam...
5
answers516
ViewsYou certainly have a right to question the charges and ask for clarification. Are these labor only charges? Is the hourly rate typical for your are...
2
answers662
ViewsTry incoming white to PES and light white, black to PES black, PES red to light black.
2
answers796
ViewsYou may also have a GFCI receptacle that has tripped. Look in bathrooms, garage, kitchen, outside.
2
answers239
ViewsMake sure you are turning the breaker completely off before trying to reset. If it continues to trip, your electrician will disconnect the wire fro...
2
answers444
Views