Posted by Dodgeman on July 22nd, 2003 12:19 PM
In reply to Auxillary Electrical Box by Dave225 on July 22nd, 2003 09:33 AM [Go to top of thread]

Use a 20 amp breaker in the main panel feeding the second panel. Then you must use at least a 12 gage wire for the 20 amp to the second panel.
Or if you us a 30 amp breaker, you must use 10 gage wire, and so on.
Dodgeman

Was this post helpful? Yes: or No: