Posted by stranded on April 18th, 2004 01:48 AM
In reply to wireing by lynn on April 18th, 2004 12:54 AM [Go to top of thread]

The problem is the terminations........

You're not allowed to put the stranded UNDER a screw..........

Some devices like GFCI's have plates under the screws...OK

Wire-nut a pigtail of solid #12 and then attach the device.......

Maybe.......Insulated StaCon? Solder?