Defective Tester


Posted by Jasper on October 28th, 2004 10:53 AM
In reply to Reversed neutral and hot by Unregistered-Larry on October 28th, 2004 02:45 AM [Go to top of thread]

Moderator Post (s) for this thread:
> That "tester" is only an indicator........ by doug seibert on 10/28/2004

The reversal of the wires should have reversed the symptoms. As Doug suggested, Get a two wire neon tester. Put one lead on the ground hole and the other to either hole in the recepticle. One should make the neon tester glow and the other not. The one that glows is the hot hole. The wire on that side of the recepticle should be a black wire connected to the "brass colored Screw", The Neutral wire goes to the "silver" screw. This is assuming that the copper wire ground wire is connected from that recepticle back to the power panel. If the ground wire is not making a connection, the neon light will not light on either hole.
Adios... Jasper