Resolved
They came back out yesterday and finally pinpointed to problem to the underground neutral feeding to my meter. There was a break in the line underground that was...
They came back out yesterday and finally pinpointed to problem to the underground neutral feeding to my meter. There was a break in the line underground that was...
5
answersI clamped the amp meter on both hot lines coming into the panel from the meter, as well as the neutral line coming from the meter. I then also put it on the grou...
5
answersThe initial cause for my concern was when I was doing plumbing work (not realizing the system was grounded through it) and took out a main section of pipe, some l...
5
answersI had a BGE (local power company) service person come out to investigate what I believe to be an open/loose neutral problem. The service person did not believe t...
5
answers