?
Generally speaking, there must be at least one switched lighting outlet in each room of a dwelling. I don't recall seeing anything in the code about home offices...
Generally speaking, there must be at least one switched lighting outlet in each room of a dwelling. I don't recall seeing anything in the code about home offices...
22
answersJustin, Unless someone here is clairvoyant, there is no way to tell you what those wires do based on color alone. There are only a few instances where speci...
3
answersThe basic reason is so that you do not kill yourself or someone else. Imagine doing what you said. Now picture that white wire becoming broken somewhere upstre...
1
answersFor the price, replacing the capacitor is worth a try. However, the windings of the motor may have already been damaged. Once you replace the cap, run the fan, bu...
5
answersEmil, If the burning smell is coming from the fan, turn off the power, take down the fan & insert it into the nearest trash can. Swing by the local Big Box...
5
answersRobert, Prices vary considerably from one part of the country to another so you should ask a few contractors for quotes on this work. Most outside breaker b...
4
answersRobert, Do you have fuses or circuit breakers? Fuses are a one time use item that is thrown away. Circuit breakers can be reset. your description sounds like y...
4
answersI'm thinking it is a loose connection. Check all spliced connections by tugging on each conductor, check the connection at the breaker and neutral bus for tightne...
4
answersThe NEC, prior to the 2005 edition requires that concealed low voltage wiring for lighting be installed as a chapter 3 wiring method. What this means is, low volt...
3
answersA #6 cable will be adequate. If you were to go for a minimalist installation, you could probably get by with smaller conductors based on the welders duty cycle. I...
2
answersOutlet A looks like a NEMA L5-30, 30 amp 1205 volt twistlock. The bent slot (3) should be the equipment ground of the remaining 2 slots, I'd guess that the widest...
4
answersYes, your plan will work and no, it won't meet code. All conductors of a circuit must be in the same cables. I'm presuming that the power goes to the switch ...
2
answersBeieng a firm believer in following instructions (at least when they apply to electrical work) I recommend that you come up with an equipment ground. You have ...
2
answersZeke, I suppose you're not lucky enough to be able to drill into the remains of the screw & use an easy out(if they're made that small)? De-energize the...
3
answersMy 2005 NEC must be missing a few pages. There are no appendix H, there isn't even an Annex H. Also, 240.100 applies for voltages greater than 600 volts. I've...
9
answersI'm presuming that you checked to see that the GFI does not protect anything downstream from itself. If that is the case and you found no problems, go ahead &...
10
answersThere should be a considerable amount of extra wire in the wall if we are, in fact, talking about the same thing. This would make it fairly easy to install a box...
4
answersLook inside the can, there shgould be a label that has all of the acceptable trims, lamp type & wattage combinations. If an R40 lamp is not one of the listed ...
3
answersI, for one, will need a lot better description of the wiring to figure out what you're getting at. "Hardwired" is a term that is generally used to mean that the e...
4
answersMy calculator shows a voltage drop of 6.5 volts (5.4%) using the numbers you posted. This is just a wee bit on the high side, but as long as you don't try to sta...
9
answers