Latest Discussions : Electrical & Lighting

jdcron

05:37PM | 01/15/15
Member Since: 01/15/15
2 lifetime posts
M Magenctek Century AC motor
Industrial Class B
Volts 120/240
Amps 15.0/7.5
Hz 60
HP SPL????
RPM 3450
Class B
Air compressor Switch
Condor 1 Phase
1 phase rating, 120volts 60Hz FLA 24 LRA 144
240 Volts 60Hz FLA 24 LRA 144
60C/75C copper wire only 10-18 AWG Torque 9lb in
Iron Force
6.25 HP
1.8 HP
28gal tank
150 Max PSI
So the compressor is tripping the breaker a few seconds after running. I have did all the trouble shooting, Good check valve, Both Caps are good, Motor was checked by AC motor tech and checked out good, good uploader valve is good. Getting 0.118 volts to the motor.
So now Im thinking an electrical problem.
Here's what I have.
Running 220 to the garage, wired to a dedicated circuit in the garage but,this circuit wire is 14-2. I m now thinking I need to change this wire to a 12-2 with a double pole 20amp breaker?
I don't think Im getting enough amps to the motor from the 14-2 wire.
email jdcron@wmis.net

jdcron

05:41PM | 01/15/15
Member Since: 01/15/15
2 lifetime posts
Oh yeah, forgot to say Im only getting 110 volts to the outlet from the breaker.

LarryG

06:20AM | 01/16/15
Member Since: 07/22/04
649 lifetime posts
" I m now thinking I need to change this wire to a 12-2 with a double pole 20amp breaker?" That's exactly what I would do. Don't forget you also need to reconfigure the unit for 240. However you could probably get by with just running 12AWG with a 20 Amp single pole.

BV006758

09:58AM | 01/16/15
Sounds like the motor is pulling extra amps to get started and tripping the breaker, or maybe a weak breaker? I would change to #12 wire with a single 20 amp breaker if you are running straight 110.
Contractor John
http://ContractorJohn.com

BV006765

11:00AM | 01/17/15
exactly what I was thinking. Thanks.


Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply choose button

Anonymous

Post new button or Login button
Register