Latest Discussions : Electrical & Lighting

ralphdellinger

02:36PM | 01/25/09
Member Since: 11/12/08
2 lifetime posts
Currently I have a room that has a 15 circuit with only 2 outlets on it. I'm making it into a bathroom/dressing room. What circuits do I require for 2 outlets near a vanity, 2 other outlets, vanity lighting, shower fan, and 4 recessed lights. The GFI's will be used for hair dryer, iron, etc. Would I need a 20 amp circuit for the 2 GFI outlets and a 15 amp for everything else? Thanks for ny input.

Billhart

09:33AM | 01/26/09
Member Since: 04/25/05
1915 lifetime posts
You need at least one 20 amp circuit to serve the bahtroom receptacles.

If there are no other bathroom connected to it you can also use it for the lights and fan.

But since you already a 15 amp circuit, have a number of lights, and both iron and hair dryer it would be a good idea to use the 15 amp circuit for the fan and lights.

And a new 20 amp circuit for the receptacles.

ralphdellinger

09:43AM | 01/26/09
Member Since: 11/12/08
2 lifetime posts
Thanks for the reply...


Post a reply as Anonymous

Photo must be in JPG, GIF or PNG format and less than 5MB.

Reply choose button

Anonymous

Post new button or Login button
Register